CBT 30 questions

First 5 of 30 questions — with answers

The correct answer is marked. Unlock the rest to study the whole test, online or offline.

  1. Question 1

    Are there any restrictions for measuring devices to be used in an Intrinsically safe loop?
    • Yes.
    • No.
    • Only when working in a zone environment.
  2. Question 2

    From where does the clearance requirement count?
    • From the centre of the housing of barrier or terminal.
    • From the «metal» in the terminal to metal.
    • From the edge of the housing of barrier or terminal.
  3. Question 3

    How many IS circuits may be routed through a junction box containing non-IS circuits without reduction of the level of protection?
    • No limitation.
    • IS circuits may never be routed through a cabinet or junction box carrying non-I. S.
    • Only 2 circuits.
    • Only one.
  4. Question 4

    How to verify how many zener diodes that are broken in a Zener barrier?
    • Megger test between IS and non-IS side.
    • There shall always be an indicator on the barrier side.
    • Unfortunatly, not possible.
  5. Question 5

    If the cable parameters are unknown, what to do?
    • Test it according to procedure in IEC 60079-14.
    • Use another cable.
    • Use the «standard» values stated in IEC 60079-14.
    • All of the options are OK.

Preview — 5 of 30 questions

You are seeing the first 5 questions with answers. Unlock the remaining 25 to study the whole test — online or offline.

About this CBT test

Exi Installation and Inspection is a CBT test with 30 questions and verified answers. Common topics include: level protection, multicore circuit, minimum creepage, circuits, earth, clearance, cable, junction.

You can practise the free questions online — one at a time, with the correct answer — or unlock the whole test and download it to study offline, without internet.

Related CBT tests