Electrical Installation in Ex-area

CBT 32 questions

First 5 of 32 questions — with answers

The correct answer is marked. Unlock the rest to study the whole test, online or offline.

  1. Question 1

    After 2008, are you allowed to install uncertified cable glands in Ex e equipment in Zone 2?
    • Yes, as long as it is made of brass.
    • No, all cable glands shall be certified.
  2. Question 2

    Can we modify the purge time on a Ex «p» enclosure?
    • Purge time is not applicable for Ex p enclosures. Only T-class.
    • No, unless the documentation from the manufacturer states otherwise.
    • Yes, adjustable depending to customer requirements.
  3. Question 3

    Can we use Ex «e» cable glands as a direct entry to a Ex «d» enclosure?
    • Depends on the Zone.
    • Yes.
    • No.
  4. Question 4

    Can you install a Ex d IIA T6 enclosure in a IIC environment?
    • No, the enclosure is not designed for IIC gasses.
    • Yes, but not for a IIB gas.
    • Yes, IIA gasses are «worse» than IIC gasses.
  5. Question 5

    Can you use greased tapes (like Denso tape) on flanged Ex d enclosures in a IIA environment?
    • Yes.
    • No.
    • Only if the gap in the enclosure is below 0,01 mm.

Preview — 5 of 32 questions

You are seeing the first 5 questions with answers. Unlock the remaining 27 to study the whole test — online or offline.

About this CBT test

Electrical Installation in Ex-area is a CBT test with 32 questions and verified answers. Common topics include: flame path, zones equipment, enclosure, enclosures, iic, environment, concept, install.

You can practise the free questions online — one at a time, with the correct answer — or unlock the whole test and download it to study offline, without internet.